Substation Trainerby Locke Design Firm / About

About Substation Trainer

Substation Trainer is a 3D training model of nine typical US substations, with linked drawings, guided lessons and practice tools. It was built by Locke Design Firm for new designers, technicians and engineers learning how substations are arranged, protected and worked on.

Content last reviewed: October 11, 2026.

DisclaimerHow to read the numbersReferencesCorrections logReport an error

Disclaimer

Substation Trainer is an educational model of typical U.S. utility practice. It is not a substitute for the applicable codes and regulations (NESC, NEC, OSHA, EPA, NERC), your utility's or employer's standards and work procedures, manufacturer instructions, or the judgment of a qualified engineer or qualified person. Dimensions, ratings and calculations are representative and are not for design, construction or field use. Working on or near energized equipment requires training, authorization and the protective measures your employer specifies under OSHA 29 CFR 1910.269 or 1910 Subpart S.

The certificate records participation in a self-paced, unproctored program. It does not make anyone a "qualified person" under OSHA; that is determined by the employer.

How to read the numbers

Values in the trainer fall into four kinds. Where it matters, the text says which kind a number is.

KindMeaningExample
Code requirementSet by law or an adopted code.OSHA minimum approach distances; NESC fence height of at least 7 ft
Standard methodFrom a consensus standard or guide.IEEE 80 touch and step limits; IEEE 998 rolling sphere
Typical practiceCommon in US utilities, but varies by company.8 ft fence (7 ft fabric + 1 ft barbed wire); 8 h battery duty cycle
Model valueA representative number chosen for the 3D model.Equipment dimensions, cable lengths, fault levels

The calculators show their equations and every input on screen: step and touch voltage (IEEE 80), arc flash (IEEE 1584-2002 equations, labeled as a teaching model), and the rolling sphere (IEEE 998).

References

Editions shown are the ones the content was checked against. Codes and standards are revised regularly: confirm the edition your project or employer has adopted. Where the edition is marked "check", the current status should be confirmed with the publisher.

Regulations

ReferenceEditionUsed for
OSHA 29 CFR 1910.269 and App. Bcurrent eCFRQualified-worker minimum approach distances (Tables R-6, R-7, altitude Table R-5), switching and grounding work practices
OSHA 29 CFR 1910.333(c)(3)current eCFRUnqualified-person distance: 10 ft up to 50 kV, plus 4 in per 10 kV above
OSHA 29 CFR 1910.151(c)current eCFREyewash near battery electrolyte
EPA 40 CFR 112 (SPCC)current eCFROil spill prevention; 112.7(c) general secondary containment and the 112.7(k) alternative for oil-filled operational equipment
EPA 40 CFR 98 Subpart DDcurrent eCFRSF6 greenhouse gas reporting
NERC Reliability StandardscurrentPRC-005 protection maintenance; CIP cyber and physical security (CIP-014, CIP-015)

Codes

ReferenceEditionUsed for
National Electrical Safety Code (NESC), IEEE C22023Fence and sign rules (110A), clearances, utility work rules (Rule 410 arc flash)
NFPA 70, National Electrical Code2023 (check 2026)Scope (90.2), arc-flash labels (110.16), equipment over 1000 V (Art. 495, formerly 490), PV (690/691)
NFPA 70E, Electrical Safety in the Workplace2024Arc-flash labels (130.5(H)), shock approach boundaries (Table 130.4(E)(a)), energized work justification (110.2, 130.2)
NFPA 850, Fire Protection for Electric Generating PlantscheckPlant switchyard fire protection

IEEE and ANSI standards

StandardEditionUsed for
IEEE 80, Safety in AC Substation Grounding2013 (check status)Tolerable touch and step voltage, grid design basics
IEEE 998, Direct Lightning Stroke Shielding2012 (check)Rolling sphere radius S = 8·k·I0.65
IEEE 1427, Electrical Clearances in Air-Insulated Substations2020Phase-to-ground and phase-to-phase clearances
IEEE 605, Bus Design in Air-Insulated Substations2008Rigid bus, expansion fittings
IEEE 980, Containment and Control of Oil Spills in SubstationscheckOil containment design basis
IEEE 1584, Arc-Flash Hazard Calculations2002 equations used; 2018 is currentArc-flash calculator (teaching model)
IEEE C37.2, Device Function NumberscurrentANSI device numbers in the glossary and drawings
IEEE C57.13, Instrument TransformerscurrentCT and VT ratings, accuracy classes, secondary voltages
IEEE C57.15, Step-Voltage RegulatorscurrentRegulator ratings (kVA on the ±10% range)
IEEE C62.11 / C62.22, Surge ArresterscurrentArrester ratings and MCOV selection
IEEE 485 / 450 / 1188, Station BatteriescurrentBattery sizing, float voltage, maintenance
IEEE C37.118, SynchrophasorscurrentPMU reporting rates
ANSI C84.1, Service Voltage RangescurrentRange A and B voltage limits
ANSI C29 series, InsulatorscurrentStation post and bell dimensions

Government and design guides

Textbooks

Corrections log

DateCorrection
Oct 11, 2026Minimum approach distances above 72.5 kV corrected to OSHA 1910.269 App. B Tables R-6/R-7 (phase-to-ground, ≤900 m). The old table understated the qualified-worker MAD at 345 kV (3.07 m, now 3.41 m) and 500 kV (3.69 m, now 5.07 m). Added the 362–420 kV and 550–800 kV bands and the source on screen.
Oct 11, 2026Industrial trip trace: removed a 65K utility link that could not coordinate above the customer's 150E fuses; the utility device is now described as sized and checked on a TCC by the utility.
Oct 11, 2026Oil containment: SPCC wording corrected (general secondary containment or the 112.7(k) alternative for oil-filled equipment; 110% applies to bulk storage). Design basis attributed to IEEE 980.
Oct 11, 2026Smaller fixes: NESC fence height (7 ft overall required, 8 ft typical); box substation arrester MCOV; IEEE 80 status note; CIP-015; PMU reporting rate; IPB fault current; CCVT voltage divider; box T1 cooling ONAN/ONAF/ONAF; bus-study costs from RUS Table 4-1; charger float voltage; metering CT ratio; height above grade from RUS Table 4-7; generator MW; 40 cal/cm² wording; certificate wording.
Oct 9, 2026PT secondary (120 V phase-to-phase / 69.3 V phase-to-ground); fault-interrupting devices (breakers, reclosers and fuses, not disconnects); battery duty cycle per IEEE 485; overstatements on isolated phase bus and exothermic welds; transformer differential explanation; regulator kVA rating; exact foundation dimensions in the BOM; body weight and surface layer inputs shown for step and touch.

Report an error

If you find a value that disagrees with a code, standard or manufacturer's data, please send the page, the value and the source to Locke Design Firm. Corrections are logged above.